Maintenance-Object Repair Procedures
Table 8-331. Test #989 SNI Fiber Out of Frame Query — Continued
Error
Test
Code
Result
Description / Recommendation
2306
ABORT
A fiber link's SNI circuit pack is not responding to test requests sent by
software.
1. Run the test led switch-node for the switch node where the SNI board(s)
2. If LEDs light on other boards in the same carrier (but not on this board),
3. If no LEDs light on any board in the same carrier, fix any connectivity
2500
ABORT
Internal system error
1. Retry the command at 1-minute intervals up to 3 times.
141
FAIL
The SNI circuit pack (Endpoint 1 of the fiber link) has a fiber out-of-frame
condition, but no loss-of-signal condition. Also, a lightwave transceiver is
connected to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
2. Perform the
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
142
FAIL
The SNI circuit pack (Endpoint 1 of the fiber link) has a fiber out-of-frame
condition, but no loss-of-signal condition. Also, no lightwave transceiver is
connected to the SNI circuit pack.
1. Check that the connected circuit pack is physically installed. The
2. Perform the
3. Replace this SNI circuit pack.
4. Replace the connected circuit pack.
8-864
Issue 1 May 2002
reside to verify whether their LEDs light. If not, continue with the following
steps.
issue test board UUCSS l (#760) for the active SNC in this carrier. Wait 5
minutes, and try step 1 again. If the board's LEDs still do not light, replace
the board. (Replacing an SNI may be service interrupting. Refer to the
SNI-BD section for the procedure to replace an SNI.)
problems between this carrier and the media server. (Use list fiber-link to
determine the fiber connections to this carrier.) Check the LEDs on every
SNI and EI, and fix any fiber problems. Enter display errors, and resolve
any SYNC, SNI-BD, SNC-BD, FIBER-LK, or SNI-PEER error entries.
connected circuit pack is the other endpoint of the fiber link if no DS1
CONV complex is administered (check via list fiber-link). Otherwise, if a
DS1 CONV complex is administered, the connected circuit pack is the DS1
CONV circuit pack connected to the SNI circuit pack.
''Fault Isolation for Fiber Links'' on page 4-19
connected circuit pack is the other endpoint of the fiber link if no DS1
CONV complex is administered (check via list fiber-link). Otherwise, if a
DS1 CONV complex is administered, the connected circuit pack is the DS1
CONV circuit pack connected to the SNI circuit pack.
''Fault Isolation for Fiber Links'' on page 4-19
in Chapter 5.
in Chapter 5.
Continued on next page
555-233-143