FIBER-LK (Fiber Link)
Table 8-328. Test #759 Configuration Audit — Continued
Error
Test
Code
Result
Description / Recommendation
238
FAIL
The physical location of SNI Endpoint 2's neighbor does not match its
administered location. (Enter list fiber-link to display a fiber link's endpoints.)
One location (carrier and slot) is assigned for the endpoint's neighbor, but it
physically resides in another location.
1. Enter list fiber-link, and verify that the fiber-optic and metallic cables are
2. If the problem does not seem to be caused by either a physical-connection
239
FAIL
The SNI Endpoint 2 is assigned to be connected to a DS1 CONV, but is not
physically connected to one. (Enter list fiber-link to display a fiber link's
endpoints.)
If this SNI endpoint should be connected to a DS1 CONV:
1. Issue list fiber-link to verify that the fiber-optic cable and/or metallic cable
If not, change administration to remove the DS1 converter complex from the
SNI's fiber link by:
1. Issuing list fiber-link to locate this SNI endpoint's fiber
2. Issuing remove fiber-link for this SNI endpoint's fiber
3. Issuing add fiber-link to replace the fiber without assigning the DS1
240
FAIL
The SNI Endpoint 2 is physically connected to a DS1 CONV, but is not
assigned to be connected to one. (list fiber-link can be used to display a fiber
link's endpoints.)
Either, replace the DS1 CONV with fiber by:
1. Issuing list fiber-link to verify that the fiber-optic and metallic cable
2. Disconnecting the SNI endpoint from the DS1 CONV
3. Issuing add fiber-link to reconnect the SNI to its assigned fiber
Or, add a DS1 converter complex to the SNI's fiber by:
1. Issuing list fiber-link to locate this SNI endpoint's fiber
2. Issuing remove fiber-link for this SNI endpoint's fiber
3. Issuing add fiber-link, both to replace the fiber and to assign the DS1
PASS
The administered data and the circuit packs the SNI(s) can communicate with
match.
555-233-143
installed as administered.
or an administration problem, replace the neighbor circuit pack. The
neighbor circuit pack may have a hardware problem causing it to report a
wrong angel address (physical carrier/slot address) to software.
connections are installed as assigned.
converter complex.
connections are installed as assigned
Converter complex
Continued on next page
Issue 1 May 2002
8-859