Avaya S8700 Maintenance Manual page 1632

For multi-connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Maintenance-Object Repair Procedures
Table 8-350. Test #6 NPE Crosstalk Test — Continued
Error
Test
Code
Result
Description / Recommendation
0
NO
The test could not relate the internal ID to the port (no board). This could be
BOARD
due to incorrect translations, no board is inserted, an incorrect board is
inserted, or an insane board is inserted.
1. Check to ensure that the board translations are correct. Use the list
2. If the board was found to be correctly inserted in step 1, issue the busyout
3. Issue the reset board command.
4. Issue the release busy board command.
5. Issue the test board long command. This should re-establish the linkage
Hybrid Electronic Power Feed Test (#56)
In this test, the software requests that the EPF be turned on for a given port. Then
hardware attempts to turn on the power unit from the station. If no current is
drawn, the station is probably not connected. If an overcurrent condition is
sensed (that is, too much current is being drawn), this may indicate a short in the
loop or a defective voice terminal. A message is returned stating that either the
EPF was turned on successfully, or that an overcurrent condition exists. This test
is repeated once more 5 seconds later. If either test is not successful, the test will
abort (see first ABORT entry in
Table 8-351. Test #56 Hybrid Electronic Power Feed Test
Error
Test
Code
Result
Description / Recommendation
ABORT
Internal system error
1. Retry the command at 1-minute intervals up to 5 times.
8-910
Issue 1 May 2002
config command, and resolve any problems that are found.
board command.
between the internal ID and the port. If this is not the case, dispatch to
check to ensure that there is a valid board inserted.
Table 8-351 on page
Continued on next page
8-910).
Continued on next page
555-233-143