CLAN-BD (Control LAN Circuit Pack)
Link Status Test (#601)
This nondestructive test determines the state of the call-control signaling link for
Control LANs. If the signaling link is physically connected, the test sends a test
frame over the link and checks for a response. The test passes only if both the
signaling link is connected and the test frame is successfully transmitted.
A failure may indicate a problem with:
this circuit pack
the packet bus
the Packet Interface circuit pack
Table 8-174. Test #601 Link Status Test
Error
Test
Code
Result
Description / Recommendation
1125
ABORT
RSCL link or C-LAN board not in service.
1. Release the board.
2. Repeat the test.
3. Escalate if the problem persists.
2012
ABORT
Could not allocate the necessary system resources to run this test.
2100
ABORT
Internal system error.
1. Retry command at 1-minute intervals up to 5 times.
2. If the problem persists, escalate the problem.
2
FAIL
The RSCL control link disconnected.
1. Retry command at 1-minute intervals up to 5 times.
2. If the test continues to fail, execute Packet Interface test (#598) (test
3. If Packet Interface test (#598) fails, see
4. If Packet Interface test (#598) passes, refer to Packet Control circuit pack
3
FAIL
Received no response to RSCL control link test frame.
1. Retry command at 1-minute intervals up to 5 times.
2. If the problem persists, reset the circuit pack (reset board UUCSS).
3. If test continues to fail, replace the circuit pack.
PASS
RSCL control link connected.
555-233-143
board UUCSS) to determine whether the problem is due to the circuit
pack.
page 8-1238
for repair procedures.
and packet-bus repair procedures.
''PKT-INT (Packet Interface)'' on
Continued on next page
Issue 1 May 2002
8-427