Avaya S8700 Maintenance Manual page 1340

For multi-connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Maintenance-Object Repair Procedures
Table 8-248. Test #141 Yellow Alarm Inquiry Test — Continued
Error
Test
Code
Result
Description / Recommendation
PASS
No Yellow alarm nor Remote Multiframe Alarm nor F5 State Alarm is received
from the remote DS1 endpoint.
0
NO
The test could not relate the internal ID to the port (no board).
BOARD
This could be due to incorrect translations, no board is inserted, an incorrect
board is inserted, or an insane board is inserted.
1. Verify that the board's translations are correct. Use the add ds1 UUCSS
2. If board was already administered correctly, check the error log to
3. If the board was found to be correctly inserted in step 1, issue the busyout
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
Major Alarm Inquiry Test (#142)
The Major alarm raised by a DS1 Interface circuit pack indicates that the average
bit error rate on the DS1 facility is greater than 1/1000. The Major Alarm Inquiry
test is used to determine that the received DS1 bit error rate is greater than
1/1000. When D4 framing mode is selected, the DS1 Interface circuit pack takes
16 seconds to recognize and report a Major alarm and 16 seconds to recognize
and report that a Major alarm condition is cleared. If ESF framing mode is
selected, the DS1 Interface circuit pack takes 10 seconds to recognize and report
a Major alarm and 10 seconds to recognize and report that a Major alarm
condition is cleared.
When the DS1 Interface circuit pack detects a Major alarm, it will send a
MAJOR-ALARM message to the maintenance software. After the maintenance
software receives a MAJOR-ALARM message, the Major Alarm Inquiry test is
initiated to confirm the Major alarm on the DS1 Interface circuit pack. The Inquiry
test will be run every 10 minutes until the Major alarm is cleared. The
maintenance software places all trunks on the circuit pack in the out-of-service
state if the Major alarm persists for more than 20 minutes.
8-618
Issue 1 May 2002
command to administer the DS1 interface if it is not already administered.
determine whether the board is hyperactive. If so, the board was shut
down. Reseating the board will re-initialize it.
board command.
This should re-establish the linkage between the internal ID and the port.
Continued on next page