CARR-POW (Carrier Power Supply)
Off-Line Switcher (OLS) Query Test (#127)
This test queries the the EPN's Maintenance for the status of the pair of OLSs in
the specified carrier. If both OLSs are on and functioning, then the test passes. If
both are not on and functioning, it fails.
Table 8-165. Test #127 OLS Query Test
Error
Test
Code
Result
Description / Recommendation
1000
ABORT
System resources required for this test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2000
ABORT
Response to the test request was not received within the allowable time period.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to ABORT with error code 2000, check for system
3. If the test continues to ABORT with a 2000 error code, resolve any errors
2029,
ABORT
Internal system error
2500
1. Retry the command at 1-minute intervals up to 5 times.
FAIL
AC-POWERED SYSTEMS
There is a problem with one or both OLSs on the tested carrier.
1. For each OLS that has every status LED OFF, check the AC input to the
2. At this point, AC should be present at the OLS outlet. Use the recycle
3. Unplug both OLSs, and wait approximately 1-minute to allow the OLSs to
555-233-143
powering problems with the EPN's A carrier. Resolve every AC-POWER
and CARR-POW alarm in a multicarrier-cabinet system or DC-POWER
alarm in a single-carrier cabinet system. Then, repeat the test.
against the EPN's MAINT (Maintenance circuit pack). Then, repeat the
test.
OLS at the OLS outlet. If there is no AC, then check the appropriate fuses
for the affected OLS. Replace open fuses. If the fuses open again or AC
does not show up at the OLS outlet, then there is probably a power wiring
problem in the cabinet.
carrier UUC command (where UUC is the appropriate cabinet and carrier)
in an attempt to bring back the OLSs for this carrier. If the test passes, the
trouble is cleared. If the test does not pass, one OLS or both, in the tested
carrier is defective. If only one OLS is defective, then the status LEDs on
the healthy OLS will light green for a moment. When the recycle test
determines that both OLSs are defective, the software will turn off power to
both the good and defective OLSs. This will cause the status LED(s) on
the good OLS to light red.
cool down. Plug in the OLSs. If either OLS is operating properly (the
status LEDs show green), then replace the defective OLS(s). See OLS
Replacement Procedures in this section.