Anl-16-L (16-Port Analog Line) - Avaya S8700 Maintenance Manual

For multi-connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Maintenance-Object Repair Procedures

ANL-16-L (16-Port Analog Line)

MO's Name (in
Alarm Log)
ANL-16-L
ANL-16-L
1.
UU is the universal cabinet number (1–64 for ATM PNC, 1–44 for CSS PNC). C is the carrier
designation (A, B, C, D, or E). SS is the number of the slot where the circuit pack resides (01–21).
pp is the 2-digit port number (01, 02,...).
The circuit packs listed below provide 16 analog line ports for single-line voice
terminals. The table below indicates which circuit packs are equipped with
lightning protection (for off-premises, out-of -building stations), and which ones
support the neon message waiting lamp feature.
16-Port Analog Line Circuit Packs
Circuit
Pack
TN468B
TN479
TN746
TN746B
TN2135
TN2144
TN2149
TN2180
No maintenance of the terminal connected to the 16-Port Neon Analog Line circuit
pack is performed, except to determine whether or not the terminal is connected.
Failures of the neon message waiting lamp power and the common ringing
application circuitry are reported as part of common port circuit pack errors; see
errors 1281 and 1793 in
Ringing Caused by Maintenance Testing
Test #48 may cause some terminal equipment to ring briefly during daily
maintenance. If this ringing is disturbing the customer or the terminal equipment,
it should be disabled in the Tests field of the change station extension form. Be
aware that this action will also disable Tests #6, 7, 161, and 35.
8-46
Issue 1 May 2002
Alarm Level
Initial Command to Run
MINOR
test port UUCSSpp l
WARNING
test port UUCSSpp sh
Off-
Premises
Neon
y
y
y
y
y
y
y
y
''XXX-BD (Common Port Circuit Pack)'' on page
1
Full Name of MO
16-Port Analog Line
16-Port Analog Line
8-1872.