Maintenance-Object Repair Procedures
Table 8-164. Test #126 OLS Recycle Test — Continued
Error
Test
Code
Result
Description / Recommendation
2029,
ABORT
Internal system error
2319,
1. Retry the command at 1-minute intervals up to 5 times.
2320,
2500
FAIL
There is a problem with one or both OLSs on the cycled carrier.
1. Since the OLS Recycle test failed, both OLSs in the cycled carrier should
2. If Test #127 fails, follow the repair procedures described for Test #127.
PASS
Both OLSs in the recycled carrier were found to be healthy by an EPN's
Maintenance circuit pack after the OLSs were powered down and back up. If
the status LEDs on both OLSs are not showing amber, then the MAINT
(Maintenance) circuit pack may have incorrectly reported the state of the OLSs.
Resolve any alarms on these MOs.
8-406
Issue 1 May 2002
have been powered off by the system software. Both OLSs should be
showing a red status LED, instead of an amber one. Since the OLS Query
test is a subset of the OLS Recycle test, the OLS Query test (#127) should
also fail. Run the OLS Query test by using the test environment UU
command where UU is the appropriate cabinet number.
Continued on next page
555-233-143