Advertisement

DS1-BD (DS1 Interface Circuit Pack)
Table 8-239. DS1 Interface Circuit Pack Maintenance Error Log Entries — Continued
Error
Aux
Type
Data
Associated Test
3901(v)
Any
Far CSU Loopback test
(#1213)
3902(w)
Any
One-Way Span test
(#1214)
3999 (x)
Any
None
1.
Run the short test sequence first. If every test passes, run the long test sequence. Refer to the appropriate test's
description and follow the recommended procedures.
Notes:
a. This error indicates that the circuit pack has stopped functioning or is not
completely administered. The alarm is logged about 15 minutes after the
circuit pack has been removed or 11 minutes after the SAKI test (#53) fails.
To be completely administered, a DS1 circuit pack must meet all 3 of the
following conditions:
1. Have an entry in the circuit plan via the change circuit pack
2. Be administered via the add ds1 UUCSS command
3. Be physically inserted in the appropriate slot
If the circuit pack has an entry in the circuit plan and either of the other two
conditions are not met, a MINOR alarm is logged. To resolve the error,
either:
1. Make sure all conditions for administration are met and that a
2. Completely remove the DS1-BD from the system using the following
If all the administration conditions are met for this circuit pack and the red
LED is still on, follow the instructions in
Entry or with Error Type
555-233-143
Alarm Level
command
functioning DS1 circuit pack is inserted in the correct slot.
steps:
a. Remove any administered DS1 trunks or access endpoints
associated with the circuit pack from their trunk groups.
b. Execute the remove ds1 UUCSS and change circuit pack
UUCSS commands.
1''.
On/Off
Board
Test to Clear Value
Continued on next page
''LED Alarms without Alarm Log
Issue 1 May 2002
8-591