Maintenance-Object Repair Procedures
Packet Interface Test (#598)
This nondestructive test checks the packet-bus interface circuitry on the C-LAN
circuit pack. Test failure indicates faulty circuit pack.
Table 8-172. Test #598 Packet Interface Test
Error
Test
Code
Result
Description / Recommendation
2000
ABORT
Did not receive circuit pack test response within the allowable time period.
1. Retry command at 1-minute intervals up to 5 times.
2. If the problem persists, reset the circuit pack (reset board UUCSS).
3. If the problem persists, replace the circuit pack.
2012
ABORT
Could not allocate the necessary system resources to run test.
2100
ABORT
Internal system error.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the problem persists, escalate the problem.
FAIL
Circuit pack has detected a failure of Packet Interface Test #598.
1. Retry command at 1-minute intervals up to 5 times.
2. If the problem persists, reset the circuit pack (reset board UUCSS).
3. If the test continues to fail, replace the circuit pack.
PASS
Packet Interface Test #598 passed.
8-424
Issue 1 May 2002
Continued on next page
555-233-143