Maintenance-Object Repair Procedures
Table 8-255. Test #1210 CSU Equipment Loop-Back Test — Continued
Error
Test
Code
Result
Description / Recommendation
FAIL
DS1 Interface circuit pack failed the CSU Equipment Loopback test.
1. Retry test ds1-loop UUCSS ds1/csu-loopback-tests.
2. If the ELB test continues to fail, then either the TN767E board, the CSU
3. If the ELB test continues to fail, then replace the TN767E board and run
4. If the ELB test continues to fail, the problem could be in the I/O cable
PASS
The ELB test executed successfully. The test pattern was transmitted and
received successfully over the connection from the TN767E DS1 board to the
near-edge of the 120A1 CSU module/T1 sync splitter.
0
NO
The test could not relate the internal ID to the port (no board).
BOARD
This could be due to incorrect translations, no board is inserted, an incorrect
board is inserted, or an insane board is inserted.
1. Verify that the board's translations are correct. Use the add ds1 UUCSS
2. If board was already administered correctly, check the error log to
3. If the board was found to be correctly inserted in step 1, issue the busyout
4. Issue the reset board command.
5. Issue the release busy board command.
6. Issue the test board long command.
8-636
Issue 1 May 2002
module/T1 sync splitter, or the I/O cable between the backplane and the
120A1 CSU module or the 401A T1 sync splitter (or any combination
thereof) has failed. Attempt to isolate the problem to one of these areas.
Replace the CSU module/T1 sync splitter, and run test ds1-loop UUCSS
ds1/csu-loopback-tests again.
test ds1-loop UUCSS ds1/csu-loopback-tests again.
between the backplane and the 120A1 CSU module or the 401A T1 sync
splitter.
command to administer the DS1 interface if it is not already administered.
determine whether the board is hyperactive. If so, the board was shut
down. Reseating the board will re-initialize it.
board command.
This should re-establish the link between the internal ID and the port.