ATM-SYNC (ATM Synchronization)
4. Investigate any other SYNC errors.
f. Error Type 2049: the ATM Expansion Interface circuit packs have errors
that affect synchronization. Test the ATM Expansion Interface circuit pack
with the test board UUCSS command.
This error is cleared by a "leaky bucket" strategy and takes up to one hour
to clear (leak away) the error counter once it is cleared.
g. Error Types 1, 257, and 513: noise on the DS1 line can cause transient
alarms on synchronization. Therefore, when a synchronization problem
occurs on Error Types 1, 257, or 513, a WARNING alarm is first raised for
15 to 20 minutes before the alarm is upgraded to a MINOR or MAJOR
alarm.
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented below when inspecting errors in
the system.
Order of Investigation
Test Synchronization test (#417)
1.
D = Destructive, ND = Non-destructive
Test Synchronization Test (#417)
This test updates all the Synchronization Maintenance component circuit packs
with the correct information regarding their role in providing synchronization for
the system. All the Tone-Clock, ATM Expansion Interface, DS1 Interface, and
UDS1 Interface circuit packs in the system are updated through this test. This test
either passes or aborts.
555-233-143
For Simplex Tone-Clock circuit packs in the master port network:
replace the primary and secondary (if administered) DS1 Interface
circuit packs.
Short Test
Long Test
Sequence
Sequence
X
X
Issue 1 May 2002
1
D/ND
ND
8-269