Maintenance-Object Repair Procedures
Cabinet Temperature Query Test (#122)
This test queries an EPN's Maintenance circuit pack for the status of the
temperature and fan sensors in the cabinet.
Table 8-162. Test #122 Cabinet Temperature Query Test
Error
Test
Code
Result
Description / Recommendation
1000
ABORT
System resources required to run test are not available.
1. Retry the command at 1-minute intervals up to 5 times.
2000
ABORT
Response to the test request was not received within the allowable time
period.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort with error code 2000, check for power
3. If the test continues to abort with error code 2000, check for and resolve
2029,
ABORT
Internal system error
2319,
1. Retry the command at 1-minute intervals up to 5 times.
2500
8-388
Issue 1 May 2002
problems with the EPN's A carrier. Look for and resolve every
AC-POWER and CARR-POW alarm in a multicarrier cabinet or
DC-POWER alarm in a single-carrier cabinet. Repeat the test.
every MAINT error in an EPN. Repeat the test.
Continued on next page