Avaya S8700 Maintenance Manual page 1107

For multi-connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

CABINET (Cabinet Sensors)
10. Connect the white 5-pin connector on the fan assembly. Insert and tighten
the retaining screws.
11. Replace the front fan cover, if removed.
Replacing the Fan Power Filter
The fan power filter (ED-1E554-30) is a metal box located behind the fans on the
right-hand cable trough as you face the rear of the cabinet. It is absent with
constant-speed fan assemblies.
!
CAUTION:
The fan power filter can be replaced without powering down the cabinet. To
avoid damage, you must use the following steps in the order shown. Note
that the J2F/P2F connectors on the power filter must not be connected
whenever connecting or disconnecting the J2/P2 connectors on the fan
assembly.
1. Access the power filter through the rear cabinet doors.
2. Connect the grounding wrist strap to yourself and the cabinet. The fan
alarm circuit can be damaged by ESD.
!
3. Disconnect cabinet local cable connector J2F from the P2F connector on
top of the power filter.
4. Disconnect cable connector J2 from the P2 connector on the fan assembly.
5. Loosen the power filter mounting screws using a 5/16" nut driver and
remove the filter.
!
6. Connect the J2 cable connector of the replacement power filter to the P2
connector on the fan assembly.
7. Mount the new power filter on the screws and tighten.
8. Connect cabinet local cable connector J2F to the P2F connector on the top
of the power filter.
9. The fans should start rotating after a 4 second delay.
555-233-143
CAUTION:
Failure to disconnect the J2F connector on the filter before the J2
connector on the fan assembly can damage the fan alarm circuits.
CAUTION:
Failure to connect the J2 connector on the fan assembly can damage
the fan alarm circuits.
Issue 1 May 2002