Avaya S8700 Maintenance Manual page 1411

For multi-connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

DS1 CONV-BD
The next four LEDs on the TN1654 DS1 CONV board are labeled STATUS LEDs
and are for future use. These LEDs will not be lit.
The bottom four LEDs on the TN1654 board are labeled SPAN LEDs. These
LEDs are under firmware control. If the facility is not administered, then the LED
is not lit. The LED is lit amber if the facility is running alarm free. If the facility is
detecting either a red alarm (loss-of-signal or loss-of-frame), a yellow alarm
(remote frame alarm) or a blue alarm (AIS signal) then the LED is lit red. The
SPAN SELECT Switch on the TN1654 faceplate is for future use. Pushing the
switch will have no affect on the board.
Clear Firmware-Counters Command
DS1 CONV firmware generates error reports autonomously. This takes place
independently of technician-demanded tests. Therefore, the test board UUCSS
clear command will not affect the error status reported by firmware. The clear
firmware-counters command clears every on-board firmware-detected error
unconditionally.
The clear firmware-counters UUCSS command sends a downlink message to
the DS1 CONV circuit packs, causing them to clear out their firmware error
counters and failure databases. Once the firmware failure database is cleared,
the failure audit test (#949) will pass. If problems still exist, the firmware will
increment its error counters and the failure audit test will begin failing again.
This command should not be used as a replacement for the repair procedures
associated with the hardware error log entries. This command may be useful if a
problem has been fixed and off-board alarms associated with the problem are still
active.
Downtime Required when Upgrading to TN1654
DS1 CONV Circuit Packs
!
WARNING:
Upgrading from TN574 DS1 CONV circuit packs to TN1654 DS1 CONV
circuit packs will require down time for the affected PN.
The TN1654 DS1 Converter circuit pack is not compatible with the TN573 SNI
circuit pack, the TN574 DS1 CONV board, the Y-cable used to connect to the
TN574 DS1 CONV board or pre-G3V5 software. All DS1 CONV boards and
Y-cables must be upgraded. If the PN is remoted via a Center-Stage Switch, the
connected SNI must also be upgraded. A TN573B (or higher-suffixed) SNI board
must be used when connecting to a TN1654 DS1 CONV board.
The fiber-link administration for the TN574 DS1 CONV complex must be removed
via the remove fiber-link command. The Change Circuit-Pack form must be
updated to reflect that TN1654 boards are now being used. The TN1654 DS1
CONV complex can then be administered via the add fiber-link command.
555-233-143
Issue 1 May 2002
8-689