Avaya S8700 Maintenance Manual page 1677

For multi-connect configurations
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

IPSV-CTL (Ipserver Interface Control)
Error Log Entries
Whenever a IPSI interchange takes place, an error is logged against IPSV-CTL
with a code that conveys information about the cause of the interchange and
which IPSI became active. The information given in the following tables will help
to identify areas of the Alarm Log to be investigated to find the source of the
problem.
Table 8-374. Error Code Descriptions and Aux Data
Error
Code
Description
1
3wxyz
Software requested IPSI interchange / control change
50000
Craft demand interchange of IPSI to A side
51000
Craft demand interchange of IPSI to B side
60000
Daily interchange of IPSI to standby failed
61000
Daily interchange of IPSI back to previous active failed
1.
See
Table 8-375
below for encoding of the wxyz digits of the error code.
2.
Control change is moving the Archangel's functionality from the IPSI to the EI or from the EI to the IPSI.
Error Codes for Software-Requested Interchanges
Table 8-375. Encoding of Error Codes for Software Requested IPSI interchange
Field
Variable Name
w
Active IPSI post action
x
Control (Archangel) pre
and post action
555-233-143
Value
Description
0
The A-side IPSI is active after the interchange
1
The B-side IPSI is active after the interchange
0
Archangel on IPSI before and after the interchange
1
Archangel on EI before and after the interchange
2
Archangel moves to EI
3
Archangel moves to IPSI
Aux Data
2
See
Table
8-376
0
0
0
0
Continued on next page
Issue 1 May 2002
8-955