Faults and alarms
List of faults and alarms
Remedy:
- replace the firmware on the Sensor Module by an older firmware version (r0148).
- upgrade the firmware on the Control Unit (r0018).
A50001 (F)
PROFINET configuration error
Reaction:
NONE
Acknowledge:
NONE
Cause:
A PROFINET controller attempts to establish a connection using an incorrect configuring telegram. The "Shared
Device" function has been activated (p8929 = 2).
Alarm value (r2124, interpret decimal):
10: A/F-CPU configures mixed PZD/PROFIsafe telegram.
13: F-CPU and PROFIsafe is not activated (p9601.3).
15: PROFIsafe telegram of the F-CPU does not match the setting in p9501.30.
See also: p9601 (SI enable functions integrated in the drive (processor 1))
Remedy:
Check the configuration of the PROFINET controllers as well as the p8929 setting.
A50010 (F)
PROFINET Name of Station invalid
Reaction:
NONE
Acknowledge:
NONE
Cause:
PROFINET Name of Station is invalid.
Remedy:
Correct the name of the station (p8920) and activate (p8925 = 2).
See also: p8920 (PN Name of Station)
A50020 (F)
PROFINET: Second controller missing
Reaction:
NONE
Acknowledge:
NONE
Cause:
The PROFINET function "Shared Device" has been activated (p8929 = 2). However, only the connection to a PRO-
FINET controller is present.
Remedy:
Check the configuration of the PROFINET controllers as well as the p8929 setting.
F50510
FBLOCKS: Logon of the run-time group rejected
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
When the run-time groups of the free function blocks attempted to log on with the sampling time management, the
logon of at least one run-time group was rejected.
Too many different hardware sampling times may have been assigned to the free function blocks.
Remedy:
- Check number of available hardware sampling times (T_sample < 8 ms) (r7903).
F50511
FBLOCKS: Memory no longer available for free function blocks
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
When the free function blocks were activated, more memory was requested than was available on the Control Unit.
Remedy:
Not necessary.
A50513 (F)
FBLOCKS: Run sequence value already assigned
Reaction:
NONE
Acknowledge:
NONE
Cause:
An attempt was made to assign a run sequence value already assigned to a function block on this drive object to
another additional function block on the same drive object. A run sequence value can only be precisely assigned to
one function block on one drive object.
Remedy:
Set another value that is still available on this drive object for the run sequence.
A50517
FBLOCKS: Int. meas. active
Reaction:
NONE
Acknowledge:
NONE
Cause:
A Siemens internal measurement has been activated.
Remedy:
Carry out a POWER ON (power off/on) for the Control Unit involved.
3-888