Parameters
List of parameters
p1059[0...n]
Jog 2 speed setpoint / Jog 2 n_set
Access level: 2
Can be changed: T
Units group: 3_1
Min
-210000.000 [rpm]
Description:
Sets the speed/velocity for jog 2. Jogging is level-triggered and allows the motor to be incrementally moved.
Dependency:
Refer to: p1055, p1056
p1063[0...n]
Speed limit setpoint channel / n_limit setp
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.000 [rpm]
Description:
Sets the speed limit/velocity limit effective in the setpoint channel.
Dependency:
Refer to: p1082, p1083, p1085, p1086, p1088
p1070[0...n]
CI: Main setpoint / Main setpoint
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency:
Refer to: p1071, r1073, r1078
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1070[0...n]
CI: Main setpoint / Main setpoint
CU250D-2_DP_F
Access level: 3
CU250D-2_PN_F
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the main setpoint.
Examples:
r1024: Fixed speed setpoint effective
r1050: Motor. potentiometer setpoint after the ramp-function generator
Dependency:
Refer to: p1071, r1073, r1078
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
1-156
Calculated: -
Scaling: -
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: -
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 1550, 3030
Factory setting
-150.000 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3040
Factory setting
210000.000 [rpm]
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 1550, 3030
Factory setting
[0] 2050[1]
[1] 0
[2] 0
[3] 0
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 1550, 3030
Factory setting
0