p2170[0...n]
Current threshold value / I_thres
Access level: 3
Can be changed: U, T
Units group: 6_2
Min
0.00 [Arms]
Description:
Sets the absolute current threshold for the messages.
"I_act >= I_threshold p2170" (BO: r2197.8)
"I_act < I_threshold p2170" (BO: r2198.8)
Dependency:
Refer to: p2171
p2171[0...n]
Current threshold value reached delay time / t_del I_thresh rch
Access level: 3
Can be changed: U, T
Units group: -
Min
0 [ms]
Description:
Sets the delay time for the comparison of the current actual value (r0068) with the current threshold value (p2170).
Dependency:
Refer to: p2170
p2172[0...n]
DC link voltage threshold value / Vdc thresh val
Access level: 3
Can be changed: U, T
Units group: 5_2
Min
0 [V]
Description:
Sets the DC link voltage threshold value for the following messages:
"Vdc_act <= Vdc_threshold p2172" (BO: r2197.9)
"Vdc_act > Vdc_threshold p2172" (BO: r2197.10)
Dependency:
Refer to: p2173
p2173[0...n]
DC link voltage comparison delay time / t_del Vdc
Access level: 3
Can be changed: U, T
Units group: -
Min
0 [ms]
Description:
Sets the delay time for the comparison of the DC link voltage r0070 with the threshold value p2172.
Dependency:
Refer to: p2172
p2174[0...n]
Torque threshold value 1 / M_thresh val 1
Access level: 3
Can be changed: U, T
Units group: 7_1
Min
0.00 [Nm]
Description:
Sets the torque threshold value for the messages:
"Torque setpoint < torque threshold value 1 and n_set reached" (BO: r2198.9)
"Torque setpoint < torque threshold value 1" (BO: r2198.10)
"Torque setpoint > torque threshold value 1" (BO: r2198.13)
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: p0340 = 1,3,5
Scaling: p2002
Unit selection: p0505
Max
10000.00 [Arms]
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
2000 [V]
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: -
Scaling: -
Unit selection: p0505
Max
20000000.00 [Nm]
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
0.00 [Arms]
Data type: Unsigned16
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
10 [ms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
800 [V]
Data type: Unsigned16
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
10 [ms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8012
Factory setting
5.13 [Nm]
1-289