Parameters
List of parameters
r9976[0...7]
System utilization / Sys util
Access level: 3
Can be changed: -
Units group: -
Min
- [%]
Description:
Displays the system utilization.
If the utilization is greater than 100%, fault F01054 is output.
Index:
[0] = Reserved
[1] = Computing time utilization
[2] = Reserved
[3] = Reserved
[4] = Reserved
[5] = Largest total utilization
[6] = Reserved
[7] = Reserved
Dependency:
Refer to: F01054, F01205
Note:
Re index 1:
The value shows the total computing time load of the system.
Re index 5:
The total utilization is determined using all sampling times used. The largest total utilization is mapped here. The
sampling time with the largest total utilization is displayed in r9979.
Total utilization:
Computing time load of sampling time involved including load from higher-priority sampling times (interrupts).
r9999[0...99]
Software error internal supplementary diagnostics / SW_err int diag
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Diagnostics parameter to display additional information for internal software errors.
Note:
Only for internal Siemens troubleshooting.
p10001
SI delay time for test stop at DO / SI t_delay DO
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
4.00 [ms]
Description:
Sets the delay time for testing the digital output.
Within this time, for a forced checking procedure of the digital output, the signal must have been detected via the
corresponding readback input (p10047).
Dependency:
Refer to: p10003, p10007, p10017, p10046
Note:
The delay time must be set to a value greater than the debounce time (p10017).
Regardless of p10001, the forced checking procedure will pause for at least two safety monitoring clock cycles
between each stage of the test.
The test stop is only performed if the safety output is being used (see p10042).
1-450
Calculated: -
Scaling: -
Unit selection: -
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
2000.00 [ms]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [%]
Data type: Unsigned32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
500.00 [ms]