Bit 2: A ground fault test was successfully performed.
Bit 3: A ground fault was detected.
Bit 4: A test pulse longer than one sampling time has occurred
Bit field:
Bit
Signal name
00
Short-circuit test executed
01
Phase short-circuit detected
02
Ground fault test successfully performed
03
Ground fault detected
04
Identification pulse width greater than the
minimum pulse width
Note:
If the ground fault test was selected, but not successfully performed, then sufficient current will not be able to be
established during the test pulse.
p1909[0...n]
Motor data identification control word / MotID STW
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the configuration for the motor data identification.
Bit field:
Bit
Signal name
00
Stator inductance estimate no measure-
ment
02
Rotor time constant estimate no measure-
ment
03
Leakage inductance estimate no measure-
ment
05
Determine Tr and Lsig evaluation in the time
range
06
Activate vibration damping
07
De-activate vibration detection
11
De-activate pulse measurement Lq Ld
12
De-activate rotor resistance Rr measure-
ment
14
De-activate valve interlocking time mea-
surement
15
Determine only stator resistance, valve volt-
age fault, dead time
16
Short motor identification (lower quality)
17
Measurement without control parameter cal-
culation
Note:
The following applies to permanent-magnet synchronous motors:
Without de-selection in bit 11, in the closed-loop control mode, the direct inductance LD and the quadrature induc-
tance Lq are measured at a low current.
When de-selecting with bit 11 or in the U/f mode, the stator inductance is measured at half the rated motor current.
If the stator is inductance is not measured but is to be estimated, then bit 0 should be set and bit 11 should be de-
selected.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
1 signal
Yes
Yes
Yes
Yes
Yes
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
List of parameters
0 signal
No
No
No
No
No
Data type: Unsigned32
Dyn. index: MDS
Func. diagram: -
Factory setting
0000 0000 0000 0000 0000 0000
0000 0000 bin
0 signal
No
No
No
No
No
No
No
No
No
No
No
No
FP
-
-
-
-
-
FP
-
-
-
-
-
-
-
-
-
-
-
-
1-239