Parameters
List of parameters
p2040
Fieldbus interface monitoring time / Fieldbus t_monit
CU240D-2_PN
Access level: 3
CU240D-2_PN_F
Can be changed: U, T
CU250D-2_PN_F
Units group: -
Min
0 [ms]
Description:
Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Dependency:
Refer to: F01910
Note:
0: The monitoring is de-activated.
p2042
PROFIBUS Ident Number / PB Ident No.
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
Units group: -
Min
0
Description:
Sets the PROFIBUS Ident Number (PNO-ID).
SINAMICS can be operated with various identities on PROFIBUS. This allows the use of a PROFIBUS GSD that is
independent of the device (e.g. PROFIdrive VIK-NAMUR with Ident Number 3AA0 hex).
Value:
0:
1:
Notice:
For p0014 = 1, the following applies:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
Every change only becomes effective after a POWER ON.
r2043.0...2
BO: PROFIdrive PZD state / PD PZD state
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the PROFIdrive PZD state.
Bit field:
Bit
Signal name
00
Setpoint failure
02
Fieldbus oper
Dependency:
Refer to: p2044
Note:
When using the "setpoint failure" signal, the bus can be monitored and an application-specific response triggered
when the setpoint fails.
p2044
PROFIdrive fault delay / PD fault delay
Access level: 3
Can be changed: U, T
Units group: -
Min
0 [s]
Description:
Sets the delay time to initiate fault F01910 after a setpoint failure.
The time until the fault is initiated can be used by the application. This means that is is possible to respond to the
failure while the drive is still operational (e.g. emergency retraction).
1-256
SINAMICS
VIK-NAMUR
Calculated: -
Scaling: -
Unit selection: -
Max
1999999 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
100 [s]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
100 [ms]
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned8
Dyn. index: -
Func. diagram: 2410
Factory setting
-
0 signal
No
No
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 2410
Factory setting
0 [s]
FP
-
-