r2273
CO: Technology controller error / Tec_ctrl error
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: 9_1
CU240D-2_PN_F
Min
- [%]
Description:
Displays the error (system deviation) between the setpoint and actual value of the technology controller.
Dependency:
Refer to: p2263
p2274
Technology controller differentiation time constant / Tec_ctrl D comp T
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0.000 [s]
Description:
Sets the time constant for the differentiation (D component) of the technology controller.
Note:
p2274 = 0: Differentiation is disabled.
p2280
Technology controller proportional gain / Tec_ctrl Kp
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0.000
Description:
Sets the proportional gain (P component) of the technology controller.
Note:
p2280 = 0: The proportional gain is disabled.
p2285
Technology controller integral time / Tec_ctrl Tn
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the technology controller.
Notice:
The following applies for p2251 = 0:
If the output of the technology controller lies within the range of a suppression (skip) bandwidth (p1091 ... p1094,
p1101) or below the minimum speed (p1080), the integral component of the controller is held so that the controller
temporarily works as a P controller. This is necessary in order to prevent the controller from behaving in an unstable
manner, as the ramp-function generator switches to the parameterized up and down ramps (p1120, p1121) at the
same time in order to avoid setpoint steps. This state can be exited or avoided by changing the controller setpoint or
by using the start speed (= minimum speed).
Note:
When the controller output reaches the limit, the I component of the controller is held.
p2285 = 0:
The integral time is disabled and the I component of the controller is reset.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
60.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.000
Calculated: -
Scaling: -
Unit selection: -
Max
10000.000 [s]
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
0.000 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
1.000
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
30.000 [s]
1-311