Parameters
List of parameters
BI: p1140 = 1 signal:
Ramp-function generator enable.
Dependency:
Refer to: r0054, p1141, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1140[0...n]
BI: Enable ramp-function generator/inhibit ramp-function generator / RFG enable
CU250D-2_DP_F
Access level: 3
CU250D-2_PN_F
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Ramp-function generator enable.
Dependency:
Refer to: r0054, p1141, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1141[0...n]
BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
BI: p1141 = 1 signal:
Continue ramp-function generator.
Dependency:
Refer to: r0054, p1140, p1142
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The ramp-function generator is, independent of the state of the signal source, active in the following cases:
- OFF1/OFF3.
- ramp-function generator output within the suppression bandwidth.
- ramp-function generator output below the minimum speed.
1-168
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501
Factory setting
1
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 2501
Factory setting
[0] 2090.5
[1] 1
[2] 2090.5
[3] 2090.5