Parameters
List of parameters
Note:
The I_max reduction is not executed for PTC (p0601 = 1) or bimetallic NC contact (p0601 = 4).
The I_max reduction results in a lower output frequency.
If value = 0:
An alarm is output and I_max is not reduced.
If value = 1:
An alarm is output and a timer is started. A fault is output if the alarm is still active after this timer has expired.
- for KTY84, the following applies: I_max. is reduced
- for PTC, the following is valid: I_max. is not reduced
If value = 2:
An alarm is output and a timer is started. A fault is output if the alarm is still active after this timer has expired.
If value = 12:
Behavior is always the same as for value 2.
For motor temperature monitoring without temperature sensor, when switching off, the model temperature is saved
in a non-volatile fashion. When switching on, the same value (reduced by p0614) is taken into account in the model
calculation. As a consequence, the UL508C specification is fulfilled.
p0611[0...n]
I2t motor model thermal time constant / I2t mot_mod T
Access level: 3
Can be changed: C(3), U, T
Units group: -
Min
0 [s]
Description:
Sets the winding time constant.
The time constant specifies the warm-up time of the cold stator winding when loaded with the motor standstill cur-
rent (rated motor current, if the motor standstill current is not parameterized) up until a temperature rise of 63 % of
the continuously permissible winding temperature has been reached.
Dependency:
This parameter is only used for synchronous motors (p0300 = 2xx).
Refer to: r0034, p0612, p0615
Refer to: F07011, A07012, A07910
Caution:
This parameter is automatically pre-set from the motor database for motors from the motor list (p0301).
When selecting a catalog motor, this parameter cannot be changed (write protection). Information in p0300 should
be carefully observed when removing write protection.
Note:
When parameter p0611 is reset to 0, then this switches out the thermal I2t motor model (refer to p0612).
If no temperature sensor is parameterized, then the ambient temperature for the thermal motor model is referred to
p0625.
p0612[0...n]
Mot_temp_mod activation / Mot_temp_mod act
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Setting to activate the motor temperature model.
Bit field:
Bit
Signal name
00
Activating motor temperature model 1 (I2t)
01
Activate motor temperature model 2
Dependency:
Refer to: r0034, p0604, p0605, p0611, p0615, p0625, p0626, p0627, p0628
Refer to: F07011, A07012, A07910
Notice:
Re bit 00:
This bit is only automatically activated for permanent-magnet 1FT7 synchronous motors. For other permanent-
magnet synchronous motors, the user himself must activate motor temperature model 1 (I2t).
It is only possible to activate this motor temperature model (I2t) for a time constant greater than zero (p0611 > 0).
1-102
Calculated: -
Scaling: -
Unit selection: -
Max
20000 [s]
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: MDS
Func. diagram: 8017
Factory setting
0 [s]
Data type: Unsigned16
Dyn. index: MDS
Func. diagram: 8017
Factory setting
0010 bin
0 signal
No
No
FP
-
-