Remedy:
- check the motor-side converter connection for a phase-phase short-circuit.
- rule-out interchanged line and motor cables.
- check for a ground fault.
For a ground fault:
- do not enable the pulses when connecting to a rotating motor without the "Flying restart" function activated (p1200).
- increase the de-energization time (p0347).
- If required, deactivate the monitoring (p1901).
F07808 (A)
HF damping module: damping not ready
Reaction:
OFF2 (NONE, OFF1, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When switching on or in the switched-on state, the HF damping module does not return a ready signal.
Remedy:
- Check the DRIVE-CLiQ wiring to the HF damping module.
- check the 24 V supply voltage.
- if required, replace the HF damping module.
Note:
HF Damping Module
F07810
Drive: Power unit EEPROM without rated data
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
No rated data are stored in the power unit EEPROM.
See also: p0205 (Power unit application), r0206 (Rated power unit power), r0207 (Rated power unit current), r0208
(Rated power unit line supply voltage), r0209 (Power unit maximum current)
Remedy:
Replace the power unit or inform Siemens Customer Service.
A07850 (F)
External alarm 1
Reaction:
NONE
Acknowledge:
NONE
Cause:
The BICO signal for "external alarm 1" was triggered.
The condition for this external alarm is fulfilled.
See also: p2112 (External alarm 1)
Remedy:
Eliminate the causes of this alarm.
A07851 (F)
External alarm 2
Reaction:
NONE
Acknowledge:
NONE
Cause:
The BICO signal for "external alarm 2" was triggered.
The condition for this external alarm is fulfilled.
See also: p2116 (External alarm 2)
Remedy:
Eliminate the causes of this alarm.
A07852 (F)
External alarm 3
Reaction:
NONE
Acknowledge:
NONE
Cause:
The BICO signal for "external alarm 3" was triggered.
The condition for this external alarm is fulfilled.
See also: p2117 (External alarm 3)
Remedy:
Eliminate the causes of this alarm.
F07860 (A)
External fault 1
Reaction:
OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The BICO signal "external fault 1" was triggered.
See also: p2106 (External fault 1)
Remedy:
Eliminate the causes of this fault.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Faults and alarms
List of faults and alarms
3-841