Faults and alarms
List of faults and alarms
F01513 (N, A)
BICO: Interconnection cross DO with different scalings
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
The requested BICO interconnection was established. However, a conversion is made between the BICO output and
BICO input using the reference values.
An interconnection is made between different drive objects and the BICO output has different normalized units than
the BICO input or the normalized units are the same but the reference values are different.
Example 1:
BICO output with voltage normalized unit, BICO input with current normalized unit, BICO output and BICO input lie
in different drive objects. This means that the factor p2002/p2001 is calculated between the BICO output and the
BICO input.
p2002: contains the reference value for current
p2001: contains the reference value for voltage
Example 2:
BICO output with voltage normalized unit in drive object 1 (DO1), BICO input with voltage normalized unit in drive
object 2 (DO2). The reference values for voltage (p2001) of the two drive objects have different values. This means
that the factor p2001(DO1)/p2001(DO2) is calculated between the BICO output and the BICO input.
p2001: contains the reference value for voltage, drive objects 1, 2
Fault value (r0949, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
Not necessary.
A01514 (F)
BICO: Error when writing during a reconnect
Reaction:
NONE
Acknowledge:
NONE
Cause:
During a reconnect operation (e.g. while booting or downloading - but can also occur in normal operation) a param-
eter was not able to be written to.
Example:
When writing to BICO input with double word format (DWORD), in the second index, the memory areas overlap (e.g.
p8861). The parameter is then reset to the factory setting.
Alarm value (r2124, interpret decimal):
Parameter number of the BICO input (signal sink).
Remedy:
Not necessary.
F01515 (A)
BICO: Writing to parameter not permitted as the master control is active
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
When changing the number of CDS or when copying from CDS, the master control is active.
Remedy:
If required, return the master control and repeat the operation.
A01590 (F)
Drive: Motor maintenance interval expired
Reaction:
NONE
Acknowledge:
NONE
Cause:
The selected service/maintenance interval for this motor was reached.
Alarm value (r2124, interpret decimal):
Motor data set number.
See also: p0650 (Actual motor operating hours), p0651 (Motor operating hours maintenance interval)
Remedy:
carry out service/maintenance and reset the service/maintenance interval (p0651).
F01600
SI P1: STOP A initiated
Reaction:
OFF2
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on processor 1 has detected an error and initiated a STOP A.
- forced checking procedure of the safety shutdown path on processor 1 unsuccessful.
- subsequent response to fault F01611 (defect in a monitoring channel).
Fault value (r0949, interpret decimal):
0: Stop request from processor 2.
1005: Pulses suppressed although STO not selected and there is no internal STOP A present.
3-790
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013