Parameters
List of parameters
p1080[0...n]
Minimum speed / n_min
Access level: 1
Can be changed: C(1), T
Units group: 3_1
Min
0.000 [rpm]
Description:
Sets the lowest possible motor speed.
This value is not undershot in operation.
Dependency:
Refer to: p1106
Notice:
The effective minimum speed is formed from p1080 and p1106.
Note:
The parameter value applies for both motor directions.
In exceptional cases, the motor can operate below this value (e.g. when reversing).
p1082[0...n]
Maximum speed / n_max
Access level: 1
Can be changed: C(1), T
Units group: 3_1
Min
0.000 [rpm]
Description:
Sets the highest possible speed.
Example:
Induction motor p0310 = 50 / 60 Hz without output filter and Blocksize power unit
p1082 <= 60 x 240 Hz / r0313 (vector control)
p1082 <= 60 x 650 Hz / r0313 (U/f control)
Dependency:
For vector control, the maximum speed is restricted to 60.0 / (8.333 x 500 µs x r0313). This can be identified by a
reduction in r1084. p1082 is not changed in this process due to the fact that the operating mode p1300 can be
changed over.
If a sine-wave filter (p0230 = 3) is parameterized as output filter, then the maximum speed is limited corresponding
to the maximum permissible filter output frequency (refer to the filter data sheet). When using sine-wave filters
(p0230 = 3, 4), the maximum speed r1084 is limited to 70% of the resonant frequency of the filter capacitance and
the motor leakage inductance.
For reactors and dU/dt filters, it is limited to 120 Hz / r0313.
Refer to: p0230, r0313, p0322
Notice:
After the value has been modified, no further parameter modifications can be made and the status is shown in
r3996. Modifications can be made again when r3996 = 0.
Note:
The parameter applies for both motor directions.
The parameter has a limiting effect and is the reference quantity for all ramp-up and ramp-down times (e.g. down
ramps, ramp-function generator, motor potentiometer).
The parameter is part of the quick commissioning (p0010 = 1); this means that it is appropriately pre-assigned when
changing p0310, p0311, p0322.
The following limits are always effective for p1082:
p1082 <= 60 x minimum (15 x r0310, 650 Hz) / r0313
p1082 <= 60 x maximum power unit pulse frequency / (k x r0313), with k = 12 (vector control), k = 6.5 (U/f control)
During automatic calculation (p0340 = 1, p3900 > 0), the parameter value is assigned the maximum motor speed
(p0322). For p0322 = 0 the rated motor speed (p0311) is used as default (pre-assignment) value. For induction
motors, the synchronous no-load speed is used as the default value (p0310 x 60 / r0313).
For synchronous motors, the following additionally applies:
During automatic calculation (p0340, p3900), p1082 is limited to speeds where the EMF does not exceed the DC
link voltage.
p1082 is also available in the quick commissioning (p0010 = 1); this means that when exiting via p3900 > 0, the
value is not changed.
1-158
Calculated: -
Scaling: -
Unit selection: p0505
Max
19500.000 [rpm]
Calculated: p0340 = 1
Scaling: -
Unit selection: p0505
Max
210000.000 [rpm]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3050
Factory setting
0.000 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3020, 3050, 3060,
3070, 3095
Factory setting
1500.000 [rpm]