p2163[0...n]
Speed threshold 4 / n_thresh val 4
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency:
Refer to: p2164, p2166, r2197
p2164[0...n]
Hysteresis speed 4 / n_hysteresis 4
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the hysteresis speed (bandwidth) for the "speed setpoint - actual value deviation in tolerance t_off" signal/mes-
sage (BO: r2197.7).
Dependency:
Refer to: p2163, p2166, r2197
p2166[0...n]
Off delay n_act = n_set / t_del_off n_i=n_so
Access level: 3
Can be changed: U, T
Units group: -
Min
0.0 [ms]
Description:
Sets the switch-off delay time for the "speed setpoint - actual value deviation in tolerance t_off" signal/message
(BO: r2197.7).
Dependency:
Refer to: p2163, p2164, r2197
p2167[0...n]
Switch-on delay n_act = n_set / t_on n_act=n_set
Access level: 3
Can be changed: U, T
Units group: -
Min
0.0 [ms]
Description:
Sets the switch-on delay for the "speed setpoint - actual value deviation in tolerance t_on" signal/message (BO:
r2199.4).
r2169
CO: Actual speed smoothed signals / n_act smth message
Access level: 2
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the smoothed actual speed for messages/signals.
Dependency:
Refer to: p2153
1-288
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
200.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
10000.0 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
10000.0 [ms]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010
Factory setting
90.00 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010
Factory setting
2.00 [rpm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010
Factory setting
200.0 [ms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8010
Factory setting
200.0 [ms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 1750, 8010, 8012,
8013
Factory setting
- [rpm]

Advertisement

loading

This manual is also suitable for:

Cu240d-2Cu250d-2Cu240d-2 dpCu240d-2 dp fCu240d-2 pnCu240d-2 pn f ... Show all