1010: Pulses enabled although STO is selected or an internal STOP A is present.
9999: Subsequent response to fault F01611.
Remedy:
- select Safe Torque Off and de-select again.
For fault value = 9999:
- carry out diagnostics for fault F01611.
Note:
STO: Safe Torque Off
F01611 (A)
SI P1: Defect in a monitoring channel
Reaction:
NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY (POWER ON)
Cause:
The drive-integrated "Safety Integrated" function on processor 1 has detected a fault in the crosswise data compar-
ison between the two monitoring channels and has initiated a STOP F.
Fault F01600 (SI P1: STOP A initiated) is output as a consequence of this fault.
Fault value (r0949, interpret decimal):
0: Stop request from processor 2.
1 ... 999:
Number of the cross-compared data that resulted in this fault. This number is also displayed in r9795.
2: SI enable safety functions (p9601, p9801). Crosswise data comparison is only carried out for the supported bits.
3: SI F-DI changeover tolerance time (p9650, p9850).
8: SI PROFIsafe address (p9610, p9810).
9: SI debounce time for STO (p9651, p9851).
1000: Watchdog timer has expired.
Within the time of approx. 5 x p9650, alternatively, the following was defined:
- Too many signal changes have occurred at the F-DI.
- Via PROFIsafe, STO was too frequently initiated (also as subsequent response).
1001, 1002: Initialization error, change timer / check timer.
2000: Status of the STO selection for both monitoring channels are different.
2001: Feedback of the safe pulse suppression on the two monitoring channels are different.
2003: Status of the STO terminal on the processor 1 and processor 2 are different.
6000 ... 6166:
PROFIsafe fault values (PROFIsafe driver for PROFIBUS DP V1/V2 and PROFINET).
For these fault values, the failsafe control signals (failsafe values) are transferred to the safety functions.
6000: An internal software error has occurred (only for internal Siemens troubleshooting).
6064 ... 6071: Error when evaluating the F parameters. The values of the transferred F parameters do not match the
expected values in the PROFIsafe driver.
6064: Destination address and PROFIsafe address are different (F_Dest_Add).
6065: Destination address not valid (F_Dest_Add).
6066: Source address not valid (F_Source_Add).
6067: Watchdog time not valid (F_WD_Time).
6068: Incorrect SIL level (F_SIL).
6069: Incorrect F-CRC length (F_CRC_Length).
6070: Incorrect F parameter version (F_Par_Version).
6071: CRC error for the F parameters (CRC1). The transferred CRC value of the F parameters does not match the
value calculated in the PROFIsafe driver.
6072: F parameterization is inconsistent.
6165: A communications error was identified when receiving the PROFIsafe telegram. The fault may also occur if an
inconsistent or out-of-date PROFIsafe telegram has been received after switching the Control Unit off and on or after
plugging in the PROFIBUS/PROFINET cable.
6166: A time monitoring error (timeout) was identified when receiving the PROFIsafe telegram.
Remedy:
Re fault values 1 ... 999 described in "Cause":
- check the cross data comparison that resulted in a STOP F.
- carry out a POWER ON (power off/on).
For fault value = 1000:
- check the wiring of the F-DI (contact problems).
- PROFIsafe: Remove contact problems/faults at the PROFIBUS master/PROFINET controller.
Re fault value = 1001, 1002:
- carry out a POWER ON (power off/on).
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Faults and alarms
List of faults and alarms
3-791