Parameters
List of parameters
p1341[0...n]
I_max frequency controller integral time / I_max_ctrl Tn
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the integral time for the I_max frequency controller.
Dependency:
Refer to: p1340
Note:
When p1341 = 0, the current limiting controller influencing the frequency is de-activated and only the current limiting
controller influencing the output voltage remains active (p1345, p1346).
In the case of power units with regenerative feedback (PM250, PM260), current limitation control for a regenerative
load is always implemented by influencing the frequency. This current limiting function is de-activated with p1340 =
p1341 = 0.
r1343
CO: I_max controller frequency output / I_max_ctrl f_outp
Access level: 3
Can be changed: -
Units group: 3_1
Min
- [rpm]
Description:
Displays the effective frequency limit.
Dependency:
Refer to: p1340
r1344
I_max controller voltage output / I_max_ctrl U_outp
Access level: 3
Can be changed: -
Units group: 5_1
Min
- [Vrms]
Description:
Displays the amount by which the converter output voltage is reduced.
Dependency:
Refer to: p1340
p1345[0...n]
I_max voltage controller proportional gain / I_max_U_ctrl Kp
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000
Description:
Sets the proportional gain for the I_max voltage controller.
Dependency:
Refer to: p1340
Note:
The controller settings are also used in the current controller of the DC braking (refer to p1232).
p1346[0...n]
I_max voltage controller integral time / I_max_U_ctrl Tn
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the integral time for the I_max voltage controller.
Dependency:
Refer to: p1340
1-192
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
50.000 [s]
Calculated: -
Scaling: p2000
Unit selection: p0505
Max
- [rpm]
Calculated: -
Scaling: p2001
Unit selection: p0505
Max
- [Vrms]
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
100000.000
Calculated: p0340 = 1,3,4
Scaling: -
Unit selection: -
Max
50.000 [s]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 1690
Factory setting
0.300 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 1690
Factory setting
- [rpm]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 1690
Factory setting
- [Vrms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 1690
Factory setting
0.000
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 1690
Factory setting
0.030 [s]