Siemens SINAMICS G120D List Manual page 389

Hide thumbs Also See for SINAMICS G120D:

Advertisement

Re bit 02:
If it has already been activated, know-how protection can be temporarily deactivated by entering the valid password
in p7766. In this case, bit 1 = 0 and bit 2 = 1 offset.
Re bit 03:
Know-how protection cannot be deactivated, as p7766 is not entered in the OEM exception list (only the factory set-
ting is possible). This bit is only set if know-how protection is active (bit 1 = 1) and p7766 has not been entered in
the OEM exception list.
Re bit 04:
When know-how protection has been activated, the contents of the memory card (parameter and DCC data) can be
additionally protected against being used with other memory cards. This bit is only set if know-how protection is
active and p7765 = 1.
p7761
Write protection / Write protection
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Setting for activating/de-activating the write protection for adjustable parameters.
Value:
0:
1:
Dependency:
Refer to: r7760
Notice:
While write protection is active, a download is prevented; however, it is still possible to restore the factory settings.
Note:
Parameters with the "WRITE_NO_LOCK" attributes are excluded from the write protection.
A product-specific list of these parameters is also available in the corresponding List Manual.
p7762
Write protection multi-master fieldbus system access behavior / Fieldbus acc_behav
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Sets the behavior for write protection when accessing via multi-master fieldbus systems (e.g. CAN, BACnet).
Value:
0:
1:
Dependency:
Refer to: r7760, p7761
p7763
KHP OEM exception list number of indices for p7764 / KHP OEM qty p7764
Access level: 3
Can be changed: U, T
Units group: -
Min
1
Description:
Sets the number of parameters for the OEM exception list (p7764[0...n]).
p7764[0...n], with n = p7763 - 1
Dependency:
Refer to: p7764
Note:
KHP: Know-How Protection
Even if know-how protection is set, parameters in this list can be read and written to.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Deactivate write protection
Activate write protection
Write access independent of p7761
Write access dependent on p7761
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
500
Parameters
List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
1
1-389