Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
r2124[0...63]
Alarm value / Alarm value
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays additional information about the active alarm (as integer number).
Dependency:
Refer to: r2110, r2122, r2123, r2125, r2134, r2145, r2146
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
r2125[0...63]
Alarm time removed in milliseconds / t_alarm res ms
Access level: 3
Can be changed: -
Units group: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the alarm was cleared.
Dependency:
Refer to: r2110, r2122, r2123, r2124, r2134, r2145, r2146
Notice:
The time comprises r2146 (days) and r2125 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the alarm buffer and the assignment of the indices is shown in r2122.
p2126[0...19]
Setting fault number for acknowledge mode / Fault_no ackn_mode
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Selects the faults for which the acknowledge mode is to be changed
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2127
Notice:
It is not possible to re-parameterize the acknowledge mode of a fault in the following cases:
- Fault number does not exist.
- Message type is not "fault" (F).
Note:
Re-parameterization is also possible if a fault is present. The change only becomes effective after the fault has
been resolved.
p2127[0...19]
Sets acknowledgement mode / Acknowledge mode
Access level: 3
Can be changed: U, T
Units group: -
Min
1
Description:
Sets the acknowledge mode for selected fault.
Value:
1:
2:
Dependency:
Selects the faults and sets the required acknowledge mode realized under the same index
Refer to: p2126
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Acknowledgment only using POWER ON
Ack IMMEDIATELY after the fault cause has been removed
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
2
Parameters
List of parameters
Data type: Integer32
Dyn. index: -
Func. diagram: 1750, 8065
Factory setting
-
Data type: Unsigned32
Dyn. index: -
Func. diagram: 1750, 8065
Factory setting
- [ms]
Data type: Unsigned16
Dyn. index: -
Func. diagram: 1750, 8075
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: 1750, 8075
Factory setting
1
1-279