r0038
Power factor smoothed / Cos phi smooth
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays the smoothed actual power factor. This refers to the electrical power of the basic fundamental signals at
the converter output terminals.
Notice:
For infeed units, the following applies:
For active powers < 25 % of the rated power, this does not provide any useful information.
Note:
Smoothing time constant = 300 ms
The signal is not suitable as a process quantity and may only be used as a display quantity.
r0039[0...2]
Energy display / Energy displ
Access level: 2
Can be changed: -
Units group: -
Min
- [kWh]
Description:
Displays the energy values at the output terminals of the power unit.
Index:
[0] = Energy balance (sum)
[1] = Energy drawn
[2] = Energy fed back
Dependency:
Refer to: p0040
Note:
Re index 0:
Sum of the energy drawn and energy that is fed back.
p0040
Reset energy consumption display / Energy cons reset
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Setting to reset the display in r0039 and r0041.
Procedure:
Set p0040 = 0 --> 1
The displays are reset and the parameter is automatically set to zero.
Dependency:
Refer to: r0039
r0041
Energy consumption saved / Energy cons saved
Access level: 2
Can be changed: -
Units group: -
Min
- [kWh]
Description:
Displays the saved energy referred to 100 operating hours.
Dependency:
Refer to: p0040
Note:
This display is used for a fluid-flow machine.
The flow characteristic is entered into p3320 ... p3329.
For an operating time of below 100 hours, the display is interpolated up to 100 hours.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [kWh]
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
- [kWh]
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 6799, 8850, 8950
Factory setting
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [kWh]
Data type: Unsigned8
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [kWh]
1-31

Advertisement

loading

This manual is also suitable for:

Cu240d-2Cu250d-2Cu240d-2 dpCu240d-2 dp fCu240d-2 pnCu240d-2 pn f ... Show all