p0205
Power unit application / PU application
Access level: 1
Can be changed: C(1, 2)
Units group: -
Min
0
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before
and after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
1:
Dependency:
Refer to: r3996
Notice:
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note:
When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application
(p0500) and the control mode (p1300) are pre-assigned according to the selected application. The parameter has
no influence when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
r0206[0...4]
Rated power unit power / PU P_rated
Access level: 2
Can be changed: -
Units group: 14_6
Min
- [kW]
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency:
IECdrives (p0100 = 0): Units kW
NEMA drives (p0100 = 1): Units hp
Refer to: p0100, p0205
r0207[0...4]
Rated power unit current / PU PI_rated
Access level: 3
Can be changed: -
Units group: -
Min
- [Arms]
Description:
Displays the rated power unit power for various load duty cycles.
Index:
[0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = Reserved
[4] = Reserved
Dependency:
Refer to: p0205
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Load duty cycle with high overload for vector drives
Load duty cycle with low overload for vector drives
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: p0100
Max
- [kW]
Calculated: -
Scaling: -
Unit selection: -
Max
- [Arms]
Parameters
List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [kW]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 8014
Factory setting
- [Arms]
1-49