Signal targets for STW3 in Interface Mode SINAMICS
Signal
Meaning
STW3.0
1 = Fixed setp bit 0
STW3.1
1 = Fixed setp bit 1
STW3.2
1 = Fixed setp bit 2
STW3.3
1 = Fixed setp bit 3
STW3.4
1 = DDS select. bit 0
STW3.5
1 = DDS select. bit 1
STW3.6
Reserved
STW3.7
Reserved
STW3.8
1 = Technology controller enable
STW3.9
1 = DC brake enable
STW3.10
Reserved
STW3.11
1 = Droop enable
STW3.12
1 = Torque control active
STW3.13
0 = External fault 1 (F07860)
STW3.14
Reserved
STW3.15
1 = CDS bit 1
<1>
Used in telegrams 350.
1
2
PROFIdrive (PROFIBUS/PROFINET)
STW3 control word interconnection
3
4
Interconnection
[Function diagram]
[Function diagram]
parameters
internal control word
signal target
p1020[0] = r2093.0
[3010.2]
p1021[0] = r2093.1
[2513.2]
p1022[0] = r2093.2
[2513.2]
p1023[0] = r2093.3
[2513.2]
p0820 = r2093.4
[2513.2]
p0821 = r2093.5
[2513.2]
-
-
-
-
p2200[0] = r2093.8
[2513.2]
p1230[0] = r2093.9
[2513.2]
-
-
p1492[0] = r2093.11
[2513.2]
p1501[0] = r2093.12
[2513.2]
p2106[0] = r2093.13
[2513.2]
-
-
p0811[0] = r2093.15
[2513.2]
5
6
Function diagram
fp_2446_97_51.vsd
G120D CU250D-2
12.12.2012
V4.6
<1>
Inverted
[3010.2]
-
[3010.2]
-
[3010.2]
-
[3010.2]
-
[8565.2]
-
[8565.2]
-
-
-
-
-
[7958.4]
-
[7017.1]
-
-
-
[6030.1]
-
[6060.1]
-
[8060.1]
-
-
-
[8560.3]
-
7
8