Parameters
List of parameters
p2190[0...n]
Load monitoring torque threshold 3 lower / M_thresh 3 lower
Access level: 3
Can be changed: U, T
Units group: 7_1
Min
0.00 [Nm]
Description:
Sets the speed/torque envelope curve for load monitoring.
Dependency:
The following applies: p2190 < p2189
Refer to: p2184, p2189
Note:
The lower envelope curve is defined by p2186, p2188 and p2190.
p2192[0...n]
Load monitoring delay time / Load monit t_del
Access level: 3
Can be changed: U, T
Units group: -
Min
0.00 [s]
Description:
Sets the delay time to evaluate the load monitoring.
p2193[0...n]
Load monitoring configuration / Load monit config
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Sets the load monitoring configuration.
Value:
0:
1:
2:
3:
Dependency:
Refer to: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, r2198, p3230, p3231, p3232
Refer to: A07920, A07921, A07922, F07923, F07924, F07925, F07936
p2194[0...n]
Torque threshold value 2 / M_thresh val 2
Access level: 3
Can be changed: U, T
Units group: -
Min
0.00 [%]
Description:
Sets the torque threshold value for the message "Torque utilization < torque threshold value 2" (BO: r2199.11).
The message "torque setpoint < p2174" (BO: r2198.10) and "torque utilization < p2194" (BO: r2199.11) are only
evaluated after the run-up and the delay time has expired.
Dependency:
Refer to: r0033, p2195, r2199
1-294
Monitoring switched out
Monitoring torque and load drop
Monitoring speed and load drop
Monitoring load drop
Calculated: -
Scaling: -
Unit selection: p0505
Max
20000000.00 [Nm]
Calculated: -
Scaling: -
Unit selection: -
Max
65.00 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
100.00 [%]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
0.00 [Nm]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
10.00 [s]
Data type: Integer16
Dyn. index: DDS, p0180
Func. diagram: 8013
Factory setting
1
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8012
Factory setting
90.00 [%]