A30057
Power unit: Line asymmetry
Reaction:
NONE
Acknowledge:
NONE
Cause:
Frequencies have been detected on the DC link voltage that would suggest line asymmetry or failure of a line phase.
It is also possible that a motor phase has failed.
Fault F30011 is output if the alarm is present and at the latest after 5 minutes.
The precise duration depends on the power unit type and the particular frequencies.
Alarm value (r2124, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy:
- check the line phase connection.
- check the motor feeder cable connections.
If there is no phase failure of the line or motor, then line asymmetry is involved.
- reduce the power in order to avoid fault F30011.
F30071
No new actual values received from the Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
More than one actual value telegram from the power unit module has failed.
Remedy:
Check the interface (adjustment and locking) to the power unit module.
F30072
Setpoints can no longer be transferred to the Power Module
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
More than one setpoint telegram was not able to be transferred to the power unit module.
Remedy:
Check the interface (adjustment and locking) to the power unit module.
F30074 (A)
Communication error between the Control Unit and Power Module
Reaction:
NONE
Acknowledge:
IMMEDIATELY
Cause:
Communications between the Control Unit (CU) and Power Module (PM) via the interface no longer possible. The
CU may have been withdrawn or is incorrectly inserted.
Fault value (r0949, interpret hexadecimal):
0 hex:
- a Control Unit with external 24 V supply was withdrawn from the Power Module during operation.
- with the Power Module switched off, the external 24 V supply for the Control unit was interrupted for some time.
1 hex:
The Control Unit was withdrawn from the Power Module during operation, although the encoderless safe motion
monitoring functions are enabled. This is not supported. After re-inserting the Control Unit in operation, communica-
tions to the Power Module no longer possible.
20A hex:
The Control Unit was inserted on a Power Module, which has another code number.
20B hex:
The Control Unit was inserted on a Power Module, which although it has the same code number, has a different serial
number. The Control Unit executes an automatic warm restart to accept the new calibration data.
Remedy:
For fault value = 0 and 20A hex:
Insert the Control Unit on an appropriate Power Module and continue operation. If required, carry out a POWER ON
of the Control Unit.
For fault value = 1 hex:
Carry out a POWER ON of the Control Unit.
F30080
Power unit: Current increasing too quickly
Reaction:
OFF2
Acknowledge:
IMMEDIATELY
Cause:
The power unit has detected an excessive rate of rise in the overvoltage range.
- closed-loop control is incorrectly parameterized.
- motor has a short-circuit or fault to ground (frame).
- U/f operation: Up ramp set too low.
- U/f operation: rated current of motor much greater than that of power unit.