Siemens SINAMICS G120D List Manual page 604

Hide thumbs Also See for SINAMICS G120D:

Advertisement

Signal sources for PZD send signals
Signal
Description
ZSW1
Status word 1
NIST_A
Actual speed A (16 bit)
Absolute actual current, smoothed
IAIST_GLATT
MIST_GLATT
Actual torque smoothed
PIST_GLATT
Power factor, smoothed
NIST_A_GLATT
Actual speed, smoothed
MELD_NAMUR
VIK-NAMUR message bit bar
FAULT_CODE
Fault code
WARN_CODE
Alarm code
ZSW3
Status word 3
<1>
Data type according to the PROFIdrive profile: I16 = Integer16, U16 = Unsigned16.
1
2
PROFIdrive (PROFIBUS/PROFINET)
PZD send signals interconnection
PROFIdrive
Interconnection
Function diagram Data type
Signal No.
parameter
2
r2089[0]
[2452]
6
r0063[0]
-
51
r0068[1]
[6799]
53
r0080[1]
[6799]
54
r0082[1]
[6799]
57
r0063[1]
-
58
r3113
-
301
r2131
[8060]
303
r2132
[8065]
305
r0053
[2454]
3
4
PZD send word 1...8
<1>
p2051[0...7] WORD
r2053[0...7] WORD
Scaling
...
U16
-
I16
4000 hex
p2000
I16
4000 hex
p2002
Telegram assignment
I16
4000 hex
p2003
according to p0922
I16
4000 hex
p2004
[2420]
I16
4000 hex
p2000
U16
U16
U16
U16
5
6
Function diagram
fp_2450_97_61.vsd
SINAMICS G120D
12.12.2012
V4.6
PROFIdrive send
telegram
Header
Data
Trailer
PROFIBUS
PROFINET
7
8
- 2450 -