Siemens SINAMICS G120D List Manual page 516

Hide thumbs Also See for SINAMICS G120D:

Advertisement

Parameters
List of parameters
r20262
BO: INT 0 integrator at the upper limit QU / INT 0 QU
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Display parameter for the signal QU that output quantity Y of instance INT 0 of the integrator has reached the upper
limit value LU.
r20263
BO: INT 0 integrator at the lower limit QL / INT 0 QL
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Display parameter for the signal QL that output quantity Y of instance INT 0 of the integrator has reached the lower
limit value LL.
p20264
INT 0 run-time group / INT 0 RTG
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
5
Description:
Setting parameter for the run-time group in which instance INT 0 of the integrator is to be called.
Value:
5:
6:
9999: Do not calculate
p20265
INT 0 run sequence / INT 0 RunSeq
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0
Description:
Setting parameter for the run sequence of instance INT 0 within the run-time group set in p20264.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20266
CI: LVM 0 input X / LVM 0 input X
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source of input quantity X of instance LVM 0 of the double-sided limiter.
1-516
Run-time group 5
Run-time group 6
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
9999
Calculated: -
Scaling: -
Unit selection: -
Max
32000
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: Unsigned32
Dyn. index: -
Func. diagram: 7264
Factory setting
-
Data type: Unsigned32
Dyn. index: -
Func. diagram: 7264
Factory setting
-
Data type: Integer16
Dyn. index: -
Func. diagram: 7264
Factory setting
9999
Data type: Unsigned16
Dyn. index: -
Func. diagram: 7264
Factory setting
700
Data type: U32 / FloatingPoint32
Dyn. index: -
Func. diagram: 7270
Factory setting
0