Siemens SINAMICS G120D List Manual page 315

Hide thumbs Also See for SINAMICS G120D:

Advertisement

p2306
Technology controller fault signal inversion / Tec_ctrl fault inv
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0
Description:
Setting to invert the fault signal of the technology controller.
The setting depends on the type of control loop.
Value:
0:
1:
Caution:
If the actual value inversion is incorrectly selected, then the closed-loop control with the technology controller can
become unstable and can oscillate!
Note:
The correct setting can be determined as follows:
- inhibit the technology controller (p2200 = 0).
- increase the motor speed and in so doing, measure the actual value signal (of the technology controller).
- if the actual value increases with increasing motor speed, then the inversion should be switched out.
- if the actual value decreases with increasing motor speed, then the inversion should be set.
If value = 0:
The drive reduces the output speed when the actual value rises (e.g. for heating fans, intake pump, compressor).
If value = 1:
The drive increases the output speed when the actual value increases (e.g. for cooling fans, discharge pumps).
r2344
CO: Technology controller last speed setpoint (smoothed) / Tec_ctrl n_setp_sm
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
- [%]
Description:
Displays the smoothed speed setpoint of the technology controller prior to switching to operation with fault response
(see p2345).
Dependency:
Refer to: p2345
Note:
Smoothing time = 10 s
p2345
Technology controller fault response / Tech_ctrl flt resp
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0
Description:
Sets the response of the technology controller to the occurrence of fault F07426 (technology controller actual value
limited).
The fault response is executed if status bit 8 or 9 in the technology controller status word r2349 is set. If both status
bits are zero, a switch back to technology controller operation will follow.
Value:
0:
1:
2:
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
No inversion
Inversion
Function inhibited
On fault: Changeover to r2344 (or p2302)
On fault: Changeover to p2215
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
- [%]
Calculated: -
Scaling: -
Unit selection: -
Max
2
Parameters
List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]
Data type: Integer16
Dyn. index: -
Func. diagram: 7958
Factory setting
0
1-315

Advertisement

loading

This manual is also suitable for:

Cu240d-2Cu250d-2Cu240d-2 dpCu240d-2 dp fCu240d-2 pnCu240d-2 pn f ... Show all