Parameters
List of parameters
Dependency:
The parameterized fault response is only effective if the technology controller mode is set to p2251 = 0 (technology
controller as main setpoint).
Refer to: p2267, p2268, r2344
Refer to: F07426
Notice:
Dependent upon the application, the changing over of the setpoint when fault F07426 occurs can lead to the fault
condition disappearing and the re-activation of the technology controller. This can repeat itself and cause limit oscil-
lations. In this case, a different fault response or a different fixed setpoint 15 for the fault response p2345 = 2 should
be selected.
Note:
The parameterized fault response can only be achieved if the default fault response of the technology controller
fault F07426 is set to "NONE" (see p2100, p2101). If a fault response other than "NONE" is entered in p2101 for
F07426, p2345 must be set to zero.
If the fault occurs during ramping up to the starting setpoint p2302, this starting setpoint is retained as the final value
(there is no changeover to the fault response setpoint).
r2349.0...12
CO/BO: Technology controller status word / Tec_ctrl status
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Displays the status word of the technology controller.
Bit field:
Bit
Signal name
00
Technology controller de-activated
01
Technology controller limited
02
Technology controller motorized potentiom-
eter limited max.
03
Technology controller motorized potentiom-
eter limited min.
04
Technology controller speed setpoint total in
setpoint channel
05
Technology controller RFG bypassed in the
setpoint channel
06
Technology controller starting value at the
current limit
08
Technology controller actual value at the
minimum
09
Technology controller actual value at the
maximum
10
Technology controller output at the mini-
mum
11
Technology controller output at the maxi-
mum
12
Fault response active
p2502[0...n]
LR encoder assignment / Encoder assignment
CU250D-2_DP_F
Access level: 1
CU250D-2_PN_F
Can be changed: C(25)
Units group: -
Min
0
Description:
Sets the assigned encoder.
The actual value preprocessing and the closed-loop position control are carried out using the assigned encoder.
Value:
0:
1:
2:
Dependency:
Refer to: p0187, p0188
1-316
No encoder
Encoder 1
Encoder 2
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Calculated: -
Scaling: -
Unit selection: -
Max
2
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: Unsigned32
Dyn. index: -
Func. diagram: 7958
Factory setting
-
0 signal
No
No
No
No
No
No
Yes
No
No
No
No
No
Data type: Integer16
Dyn. index: DDS, p0180
Func. diagram: 4010
Factory setting
1
FP
-
-
-
-
-
-
-
-
-
-
-
-