p2037
PROFIdrive STW1.10 = 0 mode / PD STW1.10=0
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the processing mode for PROFIdrive STW1.10 "master control by PLC".
Generally, control world 1 is received with the first receive word (PZD1) (this is in conformance to the PROFIdrive
profile). The behavior of STW1.10 = 0 corresponds to that of the PROFIdrive profile. For other applications that
deviate from this, the behavior can be adapted using this particular parameter.
Value:
0:
1:
2:
Note:
If the STW1 is not transferred according to the PROFIdrive with PZD1 (with bit 10 "master control by PLC"), then
p2037 should be set to 2.
p2038
PROFIdrive STW/ZSW interface mode / PD STW/ZSW IF mode
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Sets the interface mode of the PROFIdrive control words and status words.
When selecting a telegram via p0922 (p2079), this parameter influences the device-specific assignment of the bits
in the control and status words.
Value:
0:
2:
Dependency:
Refer to: p0922, p2079
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Note:
- For p0922 (p2079) = 1, 350 ... 999, p2038 is automatically set to 0.
- For p0922 (p2079) = 20, p2038 is automatically set to 2.
It is not then possible to change p2038.
p2039
Select debug monitor interface / Debug monit select
Access level: 4
Can be changed: U, T
Units group: -
Min
0
Description:
The serial interface for the debug monitor is COM1 (commissioning interface, RS232) or COM2 (fieldbus interface,
RS485).
Value = 0: De-activated
Value = 1: COM1, commissioning protocol is de-activated
Value = 2: COM2, field bus is de-activated
Value = 3: Reserved
Note:
Value = 2 is only possible for Control Units with RS485 as a field bus interface.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Freeze setpoints and continue to process sign-of-life
Freeze setpoints and sign-of-life
Do not freeze setpoints
SINAMICS
VIK-NAMUR
Calculated: -
Scaling: -
Unit selection: -
Max
2
Calculated: -
Scaling: -
Unit selection: -
Max
2
Calculated: -
Scaling: -
Unit selection: -
Max
3
Parameters
List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
0
1-255