Dependency:
IEC drives (p0100 = 0): unit kg m^2
NEMA drives (p0100 = 1): unit lb ft^2
Refer to: p0341, p0342, p1959
Refer to: F07984
r1970[0...1]
Speed_ctrl_opt vibration test vibration frequency determined / n_opt f_vib det
Access level: 4
Can be changed: -
Units group: -
Min
- [Hz]
Description:
Displays the vibration frequencies determined by the vibration test.
Index:
[0] = Frequency low
[1] = Frequency high
Dependency:
Refer to: p1959
Refer to: F07985
r1973
Rotating measurement encoder test pulse number determined / n_opt puls no. det
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the number of pulses determined during the vibration test.
Note:
A negative signal indicates an incorrect polarity of the encoder signal.
p1974
Speed_ctrl_opt saturation characteristic maximum rotor flux / n_opt rotflux_max
Access level: 4
Can be changed: U, T
Units group: -
Min
104 [%]
Description:
Sets the maximum flux setpoint to measure the saturation characteristic.
r1979.0...11
BO: Speed_ctrl_opt status / n_opt status
Access level: 4
Can be changed: -
Units group: -
Min
-
Description:
Displays the status to check and monitor the states of speed controller optimization.
Bit field:
Bit
Signal name
00
Speed controller optimization activated
01
Speed controller optimization completed
02
Speed controller optimization interrupted
04
Encoder test active
05
Saturation char. identification active
06
Moment of inertia identification active
07
Recalc. speed controller parameters active
08
Speed controller vibration test active
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
- [Hz]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: p0340 = 1
Scaling: -
Unit selection: -
Max
120 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
- [Hz]
Data type: Integer32
Dyn. index: -
Func. diagram: -
Factory setting
-
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
120 [%]
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-
0 signal
No
No
No
No
No
No
No
No
FP
-
-
-
-
-
-
-
-
1-247

Advertisement

loading

This manual is also suitable for:

Cu240d-2Cu250d-2Cu240d-2 dpCu240d-2 dp fCu240d-2 pnCu240d-2 pn f ... Show all