p10002
SI discrepancy monitoring time (processor 1) / SI discrp t_mon P1
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
1.00 [ms]
Description:
Sets the monitoring time for the discrepancy for the digital inputs.
The signal states at the two associated digital inputs (F-DI) must assume the same state within this monitoring time.
Dependency:
Refer to: p10102
Note:
F-DI: Failsafe Digital Input
p10003
SI forced checking procedure timer / SI FCP Timer
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
0.00 [h]
Description:
Sets the time to carry out the forced checking procedure (test stop).
Within the parameterized time, the digital inputs/outputs must must have been subject to a forced checking proce-
dure at least once.
Dependency:
Refer to: p10002, p10007, p10046
p10006
SI acknowledgement internal event F-DI (processor 1) / SI ackn int evt P1
CU240D-2_DP_F
Access level: 3
CU240D-2_PN_F
Can be changed: C(95)
CU250D-2_DP_F
Units group: -
CU250D-2_PN_F
Min
0
Description:
Select a fail-safe digital input for the signal "acknowledge internal event" (internal fault).
The falling edge at this input resets the status "internal event" in the drives.
The rising edge at this input acknowledges any existing discrepancy errors.
Value:
0:
1:
2:
3:
255:
Dependency:
Refer to: p10106
Refer to: A01666, A30666
Note:
The values "static active" and "static inactive" result in an inactive function of the safe acknowledgment.
F-DI: Failsafe Digital Input
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Statically active
F-DI 0
F-DI 1
F-DI 2
Statically inact
Calculated: -
Scaling: -
Unit selection: -
Max
2000.00 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
8760.00 [h]
Calculated: -
Scaling: -
Unit selection: -
Max
255
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
500.00 [ms]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: -
Factory setting
8.00 [h]
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
1-451