Parameters
List of parameters
p7764[0...n]
KHP OEM exception list / KHP OEM excep list
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
OEM exception list (p7764[0...n] for setting parameters that should be excluded from know-how protection.
p7764[0...n], with n = p7763 - 1
Dependency:
The number of indices depends on p7763.
Refer to: p7763
Note:
KHP: Know-How Protection
Even if know-how protection is set, parameters in this list can be read and written to.
p7765
KHP memory card copy protection / KHP copy protect
Access level: 3
Can be changed: U, T
Units group: -
Min
0
Description:
Setting for activating/de-activating copy protection for the memory card.
This means that the OEM can define whether the parameters and DCC data encrypted on the memory card should
be protected before using on other memory cards.
Value:
0:
1:
Dependency:
Refer to: p7766, p7767, p7768
Note:
KHP: Know-How Protection
The memory card copy protection is only effective when the know-how protection has been activated.
p7766[0...29]
KHP password input / KHP passw input
Access level: 3
Can be changed: U, T
Units group: -
Min
-
Description:
Sets the password for know-how protection.
Example of a password:
123aBc = 49 50 51 97 66 99 dec (ASCII characters)
[0] = character 1 (e.g. 49 dec)
[1] = character 2 (e.g. 50 dec)
...
[5] = character 6 (e.g. 99 dec)
[29] = 0 dec (completes the entry)
Dependency:
Refer to: p7767, p7768
Notice:
An ASCII table (excerpt) can be found, for example, in the appendix to the List Manual.
When using the STARTER commissioning software, the password should be entered using the associated dialogs.
The following rules apply when entering the password:
- Password entry must start with p7766[0].
- No gaps are permissible in the password.
- Entering a password is completed when writing to p7766[29] (p7766[29] = 0 for passwords less than 30 charac-
ters).
1-390
Deactivating protection
Activating protection
Calculated: -
Scaling: -
Unit selection: -
Max
65535
Calculated: -
Scaling: -
Unit selection: -
Max
1
Calculated: -
Scaling: -
Unit selection: -
Max
-
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: Unsigned16
Dyn. index: p7763
Func. diagram: -
Factory setting
[0] 7766
[1...499] 0
Data type: Integer16
Dyn. index: -
Func. diagram: -
Factory setting
0
Data type: Unsigned16
Dyn. index: -
Func. diagram: -
Factory setting
-