Parameters
List of parameters
p1040[0...n]
Motorized potentiometer starting value / Mop start value
Access level: 2
Can be changed: U, T
Units group: 3_1
Min
-210000.000 [rpm]
Description:
Sets the starting value for the motorized potentiometer. This starting value becomes effective after the drive has
been powered up.
Dependency:
Only effective if p1030.0 = 0.
Refer to: p1030
p1041[0...n]
BI: Motorized potentiometer manual/automatic / Mop manual/auto
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to change over from manual to automatic when using a motorized potentiometer.
In the manual mode, the setpoint is changed using two signals - raise and lower. In the automatic mode, the set-
point must be interconnected via a connector input.
Dependency:
Refer to: p1030, p1035, p1036, p1042
Note:
The effectiveness of the internal ramp-function generator can be set in automatic mode.
p1042[0...n]
CI: Motorized potentiometer automatic setpoint / Mop auto setpoint
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the setpoint of the motorized potentiometer in the automatic mode.
Dependency:
Refer to: p1041
p1043[0...n]
BI: Motorized potentiometer accept setting value / MotP acc set val
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source to accept the setting value for the motorized potentiometer.
Dependency:
Refer to: p1044
Note:
The setting value (CI: p1044) becomes effective for a 0/1 edge of the setting command (BI: p1043).
p1044[0...n]
CI: Motorized potentiometer setting value / Mop set val
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source for the setting value for the motorized potentiometer.
Dependency:
Refer to: p1043
1-152
Calculated: -
Scaling: -
Unit selection: p0505
Max
210000.000 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: p2000
Unit selection: -
Max
-
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 3020
Factory setting
0.000 [rpm]
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 3020
Factory setting
0
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3020
Factory setting
0
Data type: U32 / Binary
Dyn. index: CDS, p0170
Func. diagram: 3020
Factory setting
0
Data type: U32 / FloatingPoint32
Dyn. index: CDS, p0170
Func. diagram: 3020
Factory setting
0