Parameters
List of parameters
Dependency:
Refer to: p2195, r2198
p2175[0...n]
Motor blocked speed threshold / Mot lock n_thresh
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold for the message "Motor blocked" (BO: r2198.6).
Dependency:
Refer to: p0500, p2177, r2198
Note:
The following applies for encoderless vector control for induction motors:
At low speeds in open-loop speed controlled operation (see p1755, p1756), a blocked motor cannot be detected.
The following applies for encoderless vector control for permanent magnet synchronous motors:
At low speeds in open-loop speed controlled operation (see p1755, p1756), a blocked motor can only be detected if
p2175 = p1755, and p1750 bit 6 is set to 1.
p2176[0...n]
Torque threshold value comparison delay time / M_thrsh comp T_del
Access level: 3
Can be changed: U, T
Units group: -
Min
0 [ms]
Description:
Sets the delay time for the comparison of the torque actual value (r0080) with torque threshold value 1 (p2174).
Dependency:
Refer to: p2174
p2177[0...n]
Motor blocked delay time / Mot lock t_del
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the delay time for the message "Motor blocked" (BO: r2198.6).
Dependency:
Refer to: p0500, p2175, r2198
Note:
The following applies for sensorless vector control:
At low speeds a locked motor can only be detected if no change is made to open-loop speed controlled operation. If
this is the case, the value in p2177 must be reduced accordingly (p2177 < p1758) before time p2177 has elapsed in
order to detect the locked state reliably.
As countermeasure, it is generally also possible to set p1750.6. This is only not permitted if the drive is slowly
reversed by the load at the torque limit (speed below p1755 for longer than p1758).
p2178[0...n]
Motor stalled delay time / Mot stall t_del
Access level: 3
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the delay time for the message "Motor stalled" (BO: r2198.7).
Dependency:
Refer to: r2198
Note:
In the open-loop speed controlled operating range (see p1755, p1756), vector control stall monitoring depends on
threshold p1745.
At higher speeds, the difference between flux setpoint r0083 and flux actual value r0084 is monitored.
1-290
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: -
Max
65.000 [s]
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
10.000 [s]
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8012
Factory setting
120.00 [rpm]
Data type: Unsigned16
Dyn. index: DDS, p0180
Func. diagram: -
Factory setting
200 [ms]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8012
Factory setting
3.000 [s]
Data type: FloatingPoint32
Dyn. index: DDS, p0180
Func. diagram: 8012
Factory setting
0.010 [s]