p2255
Technology controller setpoint 1 scaling / Tec_ctrl set1 scal
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0.00 [%]
Description:
Sets the scaling for the setpoint 1 of the technology controller.
Dependency:
Refer to: p2253
p2256
Technology controller setpoint 2 scaling / Tec_ctrl set2 scal
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0.00 [%]
Description:
Sets the scaling for the setpoint 2 of the technology controller.
Dependency:
Refer to: p2254
p2257
Technology controller ramp-up time / Tec_ctrl t_ramp-up
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0.00 [s]
Description:
Sets the ramp-up time of the technology controller.
Dependency:
Refer to: p2258
Note:
The ramp-up time is referred to 100 %.
p2258
Technology controller ramp-down time / Tec_ctrl t_ramp-dn
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: U, T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0.00 [s]
Description:
Sets the ramp-down time of the technology controller.
Dependency:
Refer to: p2257
Note:
The ramp-down time is referred to 100 %.
r2260
CO: Technology controller setpoint after ramp-function generator /
Tec_ctr set aftRFG
CU240D-2_DP
Access level: 2
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: 9_1
CU240D-2_PN_F
Min
- [%]
Description:
Sets the setpoint after the ramp-function generator of the technology controller.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
100.00 [%]
Calculated: -
Scaling: -
Unit selection: -
Max
650.00 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
650.00 [s]
Calculated: -
Scaling: PERCENT
Unit selection: p0595
Max
- [%]
Parameters
List of parameters
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
100.00 [%]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
1.00 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
1.00 [s]
Data type: FloatingPoint32
Dyn. index: -
Func. diagram: 7958
Factory setting
- [%]