p20316
NCM 0 run-time group / NCM 0 RTG
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
5
Description:
Setting parameter for the run-time group in which the instance NCM 0 of the numeric comparator is to be called.
Value:
5:
6:
9999: Do not calculate
p20317
NCM 0 run sequence / NCM 0 RunSeq
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
0
Description:
Setting parameter for the run sequence of instance NCM 0 within the run-time group set in p20316.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20318[0...1]
CI: NCM 1 inputs / NCM 1 inputs
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: T
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Sets the signal source of input quantities X0 and X1 of instance NCM 1 of the numeric comparator.
Index:
[0] = Input X0
[1] = Input X1
r20319
BO: NCM 1 output QU / NCM 1 output QU
CU240D-2_DP
Access level: 3
CU240D-2_DP_F
Can be changed: -
CU240D-2_PN
Units group: -
CU240D-2_PN_F
Min
-
Description:
Display parameter for binary quantity QU of instance NCM 1 of the numeric comparator.
QU is only set if X0 > X1.
© Siemens AG 2012 - 2013 All Rights Reserved
SINAMICS G120D List Manual (LH14), 01/2013
Run-time group 5
Run-time group 6
Calculated: -
Scaling: -
Unit selection: -
Max
9999
Calculated: -
Scaling: -
Unit selection: -
Max
32000
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Parameters
List of parameters
Data type: Integer16
Dyn. index: -
Func. diagram: 7225
Factory setting
9999
Data type: Unsigned16
Dyn. index: -
Func. diagram: 7225
Factory setting
820
Data type: U32 / FloatingPoint32
Dyn. index: -
Func. diagram: 7225
Factory setting
0
Data type: Unsigned32
Dyn. index: -
Func. diagram: 7225
Factory setting
-
1-525